Navien · Furnace troubleshooting

Concentric vent kit selection

NDF

What is going on

Approved concentric vent termination kits for this furnace series.

Check in this order

  1. Use a 2 in IPEX vent kit #196005 or a 3 in IPEX vent kit #196006.
  2. If using 1-1/2 in vent material with a concentric kit, use an increase coupling to connect to the 2 in concentric kit.
  3. Follow the concentric termination manufacturer instructions for installation.
  4. Keep straight vertical runs offset so condensate runs against the vent walls.

Applies to: NDF600 series furnaces with concentric venting

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.