Navien · Furnace troubleshooting
Concentric vent kit selection
What is going on
Approved concentric vent termination kits for this furnace series.
Check in this order
- Use a 2 in IPEX vent kit #196005 or a 3 in IPEX vent kit #196006.
- If using 1-1/2 in vent material with a concentric kit, use an increase coupling to connect to the 2 in concentric kit.
- Follow the concentric termination manufacturer instructions for installation.
- Keep straight vertical runs offset so condensate runs against the vent walls.
Applies to: NDF600 series furnaces with concentric venting
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.