Navien · Furnace troubleshooting
Combustion air inlet protection for non-direct vent
What is going on
Protect the combustion air inlet from blockage when using indoor combustion air.
Check in this order
- If supplying combustion air through the top of the furnace, use a double elbow arrangement.
- If supplying combustion air through the side, use a single elbow pointing downward.
- Install and secure an 8 in (20 cm) piece of intake pipe with a 90 degree elbow to keep objects out of the burner area.
- If outside wall grills are used, size them for 50 percent free area, since most sidewall grills have only 50 percent free area.
- Example a 100,000 Btu/hr unit needing a pair of 8 in round pipes may use an 8 in x 7 in equivalent duct, which requires 14 in x 8 in grills at 50 percent free area.
Applies to: NDF600 series furnaces, non-direct vent installations
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 24, 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.