Combustion air in an unconfined space (Case 1)

NDF

What is going on

Unconfined space needs at least 50 cubic feet per 1,000 Btu/hr of all fuel burning appliances in the area. Outdoor air may still be needed in airtight homes.

Likely causes

  • Insufficient combustion or ventilation air for the furnace and other fuel burning appliances

Check in this order

  1. Calculate the total input of all fuel burning appliances in the unconfined area.
  2. Confirm the space is at least 50 cubic feet per 1,000 Btu/hr.
  3. If air is insufficient, supply it from outdoors using the confined space criteria.
  4. Test furnace operation with fireplace dampers open, clothes dryer running, bathroom exhaust fans on and kitchen range hood on.

Applies to: NDF600 series furnaces using indoor combustion air

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF Forced Air Gas Furnace Installation and Operation Manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.