Combustion air in an unconfined space (Case 1)
What is going on
Unconfined space needs at least 50 cubic feet per 1,000 Btu/hr of all fuel burning appliances in the area. Outdoor air may still be needed in airtight homes.
Likely causes
- Insufficient combustion or ventilation air for the furnace and other fuel burning appliances
Check in this order
- Calculate the total input of all fuel burning appliances in the unconfined area.
- Confirm the space is at least 50 cubic feet per 1,000 Btu/hr.
- If air is insufficient, supply it from outdoors using the confined space criteria.
- Test furnace operation with fireplace dampers open, clothes dryer running, bathroom exhaust fans on and kitchen range hood on.
Applies to: NDF600 series furnaces using indoor combustion air
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF Forced Air Gas Furnace Installation and Operation Manual, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.