Combustion air in a confined space with indoor air (Case 2)

NDF

What is going on

Confined space needs two openings, one within 12 in of the ceiling and one within 12 in of the floor.

Check in this order

  1. Cut two air openings one within 12 in (305 mm) of the ceiling and one within 12 in (305 mm) of the floor.
  2. If indoor air is sufficient, size each opening at 1 square inch of free area per 1,000 Btu/hr.
  3. Include clothes dryers, bathroom fans, range hoods and other fuel burning appliances in the calculation.
  4. Make each opening at least 100 square inches, even for furnaces under 100,000 Btu/hr.

Applies to: NDF600 series furnaces using indoor combustion air

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF Forced Air Gas Furnace Installation and Operation Manual, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.