Combustible clearances and floor mounting

NDF

What is going on

Furnace may only sit on a wood floor. Keep the area clear of combustibles and storage. Service clearance overrides the combustible clearance.

Check in this order

  1. Confirm the floor is wood. Do not set the furnace on carpet, tile or any other combustible material.
  2. Check the rating plate for the certified clearance to combustibles for this model.
  3. Keep at least 24 in (610 mm) of front clearance for service access.
  4. Keep the area around the furnace free of gasoline, flammable vapors and liquids and all combustible materials.
  5. Tell the homeowner the furnace area must not be used as a closet or storage space.

Applies to: NDF600 series furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF Forced Air Gas Furnace Installation and Operation Manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.