Navien · Furnace troubleshooting
Clean the secondary heat exchanger
What is going on
The secondary heat exchanger sits directly above the blower assembly and can collect dust. Dust on warm surfaces is kept to a minimum because it can be combustible. Dust in the circulating fan reduces blower performance and efficiency.
Likely causes
- Dust build-up on the secondary heat exchanger
- Dust build-up in the circulating fan
Check in this order
- Turn off electrical power to the furnace.
- Remove the heat exchanger access door and the blower access door.
- Disconnect electrical supply before removing the burner compartment access door.
- Remove the thread covers and the screws that attach the heat exchanger to the division panel and blower assembly.
- Remove the screws that fasten the blower assembly to the division panel and heat exchanger using a 1/4 inch hex drive.
- Remove the drain hoses from the condensate trap and clean up any spillage.
- Unplug the wire harness connectors and remove the upper harness from the division panel by turning the twist-lock grommet counter-clockwise and pulling the connector through the clearance hole.
- Pull the heat exchanger assembly out.
- Vacuum the coils with the soft brush attachment.
- Slide the heat exchanger back into place using the screw holes on the division panel for alignment.
- Re-fasten the blower and heat exchanger screws from the lower vestibule through to the upper vestibule, then fit the thread covers.
- Feed the wire connectors through to the lower vestibule, secure with the twist-lock grommet, and reconnect them to the harness.
- Reconnect the condensate drain lines.
- Replace the blower and heat exchanger access doors.
- Restore electrical power and verify operation.
- Make sure the burner compartment access door is properly in place before restarting, because the gas train is designed to run as a sealed unit.
Applies to: NDF600 models
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 67-68. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.