Choosing a vent terminal location
What is going on
Pick a termination spot where flue gas cannot pool or get pulled back into the combustion air intake, and where condensate or frost will not cause damage. Moisture leaving the terminal can freeze on walls and nearby objects, and some discoloration is normal.
Likely causes
- Flue gas recirculating into the combustion air intake
- Condensate dripping onto walks, patios, planters or shrubs
- Exhaust fogging or icing near windows
- Winter winds blowing vent products back onto the terminal
Check in this order
- Keep the terminal away from spots where flue gas can stagnate.
- Keep it clear of walkways, patios and planters where condensate will drip.
- Keep it away from shrubs and vegetation, and caulk all cracks, seams and joints within 6 ft (1.8 m) of the terminal.
- Do not put the terminal under a deck unless clearance is enough to prevent damage. Insulate any piping run under a deck and support it so condensate cannot collect and freeze.
- Do not put the terminal on the side facing prevailing winter winds.
- Keep at least 3 ft (0.9 m) from an inside corner formed by two exterior walls.
- For overhangs, keep at least 1 ft (0.3 m) vertical clearance for each 1 ft horizontal, up to 6 ft (1.8 m).
- Make sure nearby painted surfaces are in good condition. Consider sealing wood that may see flue gases.
Applies to: Direct and non-direct vent terminations
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.