Checking venting after removing an old furnace
What is going on
When an existing furnace is taken out of a shared venting system, the remaining appliances may no longer vent properly. Test the remaining appliances with this procedure, which follows ANSI Z21.47 / CSA 2.3 section 4.23.6.
Likely causes
- Vent system is too large for the remaining attached appliances
- Blockage, restriction, leakage, corrosion or other defect in the vent system
Check in this order
- Inspect the venting system for correct size and horizontal pitch, and check for blockage, restriction, leakage, corrosion and other defects. Confirm the system meets the requirements of the new NPF unit, or replace it with a properly sized system.
- Close all building doors and windows, and the doors between the appliance space and the rest of the building, as far as practical.
- Close fireplace dampers.
- Turn on clothes dryers and any appliance not connected to the vent. Turn on range hoods and bathroom exhaust fans at maximum speed. Do not run a summer exhaust fan.
- Start the appliance being checked and set the thermostat so it runs continuously.
- After 5 minutes of main burner operation, check the draft hood relief opening of the other appliances for spillage using a match or candle flame.
- If venting is improper, correct the venting system according to the National Fuel Gas Code ANSI Z223.1/NFPA 54 or CSA B149.1-15. Resize per the appropriate table in Appendix G of the code.
- When every appliance passes, return doors, windows, exhaust fans, fireplace dampers and other gas appliances to their original condition.
Applies to: Removing an existing furnace from a shared vent system
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NPF installation and operation manual, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.