Navien · Furnace troubleshooting
Check supply duct static at the coil test hole
What is going on
Supply static is read between the furnace and cooling coil; return static is read between the filter and blower.
Likely causes
- Excessive external static causes low airflow, high temperature rise, limit trips and short equipment life.
Check in this order
- Remove the A-shaped block-off plate on the coil end.
- Drill a test hole in the plate and reinstall the plate.
- Take the supply static reading at the test hole.
- Take the return static reading between the filter and the furnace blower.
- Tape the test hole closed after the test.
Applies to: NPF700 hydro-furnace with evaporator coil
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NPF installation and operation manual, p. 52. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.