Check supply duct static at the coil test hole

NPF

What is going on

Supply static is read between the furnace and cooling coil; return static is read between the filter and blower.

Likely causes

  • Excessive external static causes low airflow, high temperature rise, limit trips and short equipment life.

Check in this order

  1. Remove the A-shaped block-off plate on the coil end.
  2. Drill a test hole in the plate and reinstall the plate.
  3. Take the supply static reading at the test hole.
  4. Take the return static reading between the filter and the furnace blower.
  5. Tape the test hole closed after the test.

Applies to: NPF700 hydro-furnace with evaporator coil

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.