Check inlet gas pressure (two-stage gas valve)
What is going on
Measure gas inlet pressure with a calibrated U-tube or digital manometer on the inlet pressure boss.
Check in this order
- Turn off gas and electrical supply to the furnace.
- Back the inlet pressure test screw out counterclockwise one turn maximum with a 3/32 in. Allen wrench.
- Attach a hose so it overlaps the boss by 3/8 in. Use a manometer with at least a 0 to 15 in. w.c. range.
- Turn on gas and power. Run the furnace and all other gas appliances on the line.
- Check the pressure boss for leaks with leak detection solution. Repair any leaks.
- Measure inlet pressure with burners firing. It must be within the rating plate range (5 to 10.5 in. w.c. natural, 11 to 13 in. w.c. LP).
- Shut off gas and power. Remove the hose and tighten the inlet pressure screw clockwise to at least 7 in-lb.
- Turn gas back on and leak test the boss again.
Applies to: Two-stage gas valve inlet pressure
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 50. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.