Navien · Furnace troubleshooting

Check inlet gas pressure (two-stage gas valve)

NDF

What is going on

Measure gas inlet pressure with a calibrated U-tube or digital manometer on the inlet pressure boss.

Check in this order

  1. Turn off gas and electrical supply to the furnace.
  2. Back the inlet pressure test screw out counterclockwise one turn maximum with a 3/32 in. Allen wrench.
  3. Attach a hose so it overlaps the boss by 3/8 in. Use a manometer with at least a 0 to 15 in. w.c. range.
  4. Turn on gas and power. Run the furnace and all other gas appliances on the line.
  5. Check the pressure boss for leaks with leak detection solution. Repair any leaks.
  6. Measure inlet pressure with burners firing. It must be within the rating plate range (5 to 10.5 in. w.c. natural, 11 to 13 in. w.c. LP).
  7. Shut off gas and power. Remove the hose and tighten the inlet pressure screw clockwise to at least 7 in-lb.
  8. Turn gas back on and leak test the boss again.

Applies to: Two-stage gas valve inlet pressure

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.