Check horizontal vent slope and support

NDF

What is going on

Confirm horizontal vent runs drain condensate back toward the furnace and are supported correctly.

Check in this order

  1. Slope horizontal piping back toward the furnace at a minimum of 1/4 in per foot (18 mm per meter).
  2. Support horizontal runs at least every 5 ft (1.524 m).
  3. Confirm there are no dips or sags in horizontal sections.
  4. Make sure the exhaust is supported before it is fitted to the inducer; the inducer must carry no weight of the vent system.
  5. Insulate vent runs in unconditioned space where freezing may occur, unless heat tape is applied.
  6. Where water may collect in horizontal runs, wrap with self regulating 3 or 5 watt heat tape that is CSA, UL or ULC listed and installed per its instructions.

Applies to: NDF600 series furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.