Navien · Furnace troubleshooting
Check horizontal vent slope and support
What is going on
Confirm horizontal vent runs drain condensate back toward the furnace and are supported correctly.
Check in this order
- Slope horizontal piping back toward the furnace at a minimum of 1/4 in per foot (18 mm per meter).
- Support horizontal runs at least every 5 ft (1.524 m).
- Confirm there are no dips or sags in horizontal sections.
- Make sure the exhaust is supported before it is fitted to the inducer; the inducer must carry no weight of the vent system.
- Insulate vent runs in unconditioned space where freezing may occur, unless heat tape is applied.
- Where water may collect in horizontal runs, wrap with self regulating 3 or 5 watt heat tape that is CSA, UL or ULC listed and installed per its instructions.
Applies to: NDF600 series furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.