Navien · Furnace troubleshooting
Check furnace input rate
What is going on
Calculate input from the gas heating value and the time for the meter dial to move 1 cu ft. Adjustments to burner manifold pressure must be made with a manometer or calibrated Magnehelic gauge.
Likely causes
- Gas heating value differs from the 1,000 Btu/ft³ basis, for example 900 gives about 90% input and 1,100 gives about 110%
Check in this order
- Calculate input in Btu/hr heating value of gas (Btu/ft³) × 3600 divided by the seconds needed for 1 cu ft.
- If using SI meter units 1 cu ft = 0.0283 m³, 0.01 m³ = 0.3531 cu ft, 0.5 m³ = 1.766 cu ft.
- Compare the result with the rating plate input.
- Never adjust input above the rating plate input.
- If correction is needed, adjust manifold pressure only within ±0.3 in. w.c. of the rating label value, or change the orifice size.
- Confirm the gas supplier's heating value before adjusting.
Applies to: Furnace input verification
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 52. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.