Check furnace input rate

NDF

What is going on

Calculate input from the gas heating value and the time for the meter dial to move 1 cu ft. Adjustments to burner manifold pressure must be made with a manometer or calibrated Magnehelic gauge.

Likely causes

  • Gas heating value differs from the 1,000 Btu/ft³ basis, for example 900 gives about 90% input and 1,100 gives about 110%

Check in this order

  1. Calculate input in Btu/hr heating value of gas (Btu/ft³) × 3600 divided by the seconds needed for 1 cu ft.
  2. If using SI meter units 1 cu ft = 0.0283 m³, 0.01 m³ = 0.3531 cu ft, 0.5 m³ = 1.766 cu ft.
  3. Compare the result with the rating plate input.
  4. Never adjust input above the rating plate input.
  5. If correction is needed, adjust manifold pressure only within ±0.3 in. w.c. of the rating label value, or change the orifice size.
  6. Confirm the gas supplier's heating value before adjusting.

Applies to: Furnace input verification

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.