E12 High limit stat open
What the control is telling you
Lockout: the supply temperature got too high and the high limit tripped.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
Likely causes
- Air in the system
- Dirty pump impeller
- Dirty internal filter
- Unbalanced or restricted flow
Test and repair steps
- Check the automatic de-aerator; replace if needed and run the 17-minute de-aeration program.
- Check water flow through the system; clean the pump and filter.
- Flush the whole system.
- Check balancing valve settings.
Other codes on the same units
- E00 Poor flame formation (flame sensed with burner off)
- E02 No flame formation (ignition failure)
- E04 Voltage interruption / error read-out interrupted
- E05 Adjustment error (listed in short reference)
- E14 Supply sensor T1 fault
- E18 Maximum supply temperature exceeded
- E19 Maximum return temperature exceeded
- E28 Fan speed not reported back
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.