Rinnai · Boiler

E04 Voltage interruption / error read-out interrupted

Medium severity E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the control is telling you

Message shown when power to the boiler was cut while an error was being read, once power returns and the original error is gone.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Likely causes

  • Power switched off during an error read-out
  • Controller fault if it keeps coming back without a preceding error

Test and repair steps

  1. Press reset.
  2. Find and fix the error that preceded it.
  3. If E04 persists with no earlier error, replace the controller.

Other codes on the same units

  • E00 Poor flame formation (flame sensed with burner off)
  • E02 No flame formation (ignition failure)
  • E05 Adjustment error (listed in short reference)
  • E12 High limit stat open
  • E14 Supply sensor T1 fault
  • E18 Maximum supply temperature exceeded
  • E19 Maximum return temperature exceeded
  • E28 Fan speed not reported back

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.