Rinnai · Boiler

E18 Maximum supply temperature exceeded

High severity E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the control is telling you

The supply water temperature went above 212 F.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Likely causes

  • Sudden hydraulic shut-off (filter, pump, valve)
  • Faulty supply sensor NTC1
  • Controller fault

Test and repair steps

  1. Check the real supply temperature and look for blocked flow (filter, pump, thermostatic or service valves).
  2. Measure NTC1 resistance against the sensor table and replace if defective.
  3. Replace the control unit if the error stays.

Other codes on the same units

  • E04 Voltage interruption / error read-out interrupted
  • E05 Adjustment error (listed in short reference)
  • E12 High limit stat open
  • E14 Supply sensor T1 fault
  • E19 Maximum return temperature exceeded
  • E28 Fan speed not reported back
  • E31 Supply sensor T1 shorted
  • E32 Return sensor T2 shorted

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.