Rinnai · Boiler

E32 Return sensor T2 shorted

High severity E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the control is telling you

Error mode shows return temperature 230: sensor circuit reads as shorted.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Likely causes

  • Shorted sensor or wiring

Test and repair steps

  1. Check the sensor wiring.
  2. If wiring is fine, unplug the return sensor; E37 should then appear.
  3. Replace the sensor.

Other codes on the same units

  • E14 Supply sensor T1 fault
  • E18 Maximum supply temperature exceeded
  • E19 Maximum return temperature exceeded
  • E28 Fan speed not reported back
  • E31 Supply sensor T1 shorted
  • E36 Supply sensor T1 open
  • E37 Return sensor T2 open
  • E69 No or incorrect display

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.