Rinnai · Boiler

E14 Supply sensor T1 fault

High severity E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the control is telling you

Error mode shows supply temperature around -22 (display of -36 also noted). Points to the supply sensor, its ground connection, or the controller.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Likely causes

  • T1 flow sensor ground connection
  • T1 flow sensor failure
  • Controller failure
  • Third-party DHW control contacts not fully open (resistance across terminals 16 and 17)

Test and repair steps

  1. Open the Error chapter and note the data.
  2. Check the sensor wiring and measure sensor resistance (about 12 kOhm at 77 F).
  3. Replace the supply sensor if out of range.
  4. If a third-party DHW control is used, check for resistance across terminals 16 and 17 and make sure its contacts open fully.

Other codes on the same units

  • E02 No flame formation (ignition failure)
  • E04 Voltage interruption / error read-out interrupted
  • E05 Adjustment error (listed in short reference)
  • E12 High limit stat open
  • E18 Maximum supply temperature exceeded
  • E19 Maximum return temperature exceeded
  • E28 Fan speed not reported back
  • E31 Supply sensor T1 shorted

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.