Rinnai · Boiler
E28 Fan speed not reported back
What the control is telling you
The control receives no fan speed signal.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
Likely causes
- Fan wiring or 24 V supply fault
- Failed fan
- Vent or air intake problem causing negative pressure
Test and repair steps
- Check wiring between fan and control and the 24 V fan supply.
- If wiring and voltage are good and the error repeats, replace the fan.
- Check the vent and air intake against the installation rules before replacing the fan.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.