Rinnai · Boiler

E19 Maximum return temperature exceeded

High severity E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the control is telling you

The return water temperature went above 212 F.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Likely causes

  • External heat source feeding the return
  • Faulty return sensor NTC2
  • Controller fault

Test and repair steps

  1. Check the real return temperature and look for an outside heat source.
  2. Measure NTC2 resistance and replace if defective.
  3. Replace the control unit if the error persists.

Other codes on the same units

  • E05 Adjustment error (listed in short reference)
  • E12 High limit stat open
  • E14 Supply sensor T1 fault
  • E18 Maximum supply temperature exceeded
  • E28 Fan speed not reported back
  • E31 Supply sensor T1 shorted
  • E32 Return sensor T2 shorted
  • E36 Supply sensor T1 open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.