Rinnai · Boiler
E37 Return sensor T2 open
What the control is telling you
Error mode shows return temperature -22: sensor circuit reads open.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
Likely causes
- Open sensor or wiring
Test and repair steps
- Check the sensor wiring.
- If wiring is fine, unplug the return sensor; E32 should then appear.
- Replace the sensor.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.