Rinnai · Boiler
E02 No flame formation (ignition failure)
What the control is telling you
Lockout: the burner did not light. The boiler makes one start and several restarts with rising start load, then locks out.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
Likely causes
- Gas valve closed or no gas supply
- No power to gas valve or valve not opening
- Gas inlet pressure too low (below 7 in. W.C. / 17 mbar at start)
- Ionization cable or electrode fault, weak ionization (under 4 uA)
- O2 setting off (minimum should be 4.4% NG / 4.8% LP)
- Gas valve plug not connected or wiring broken
Test and repair steps
- Read the Error chapter data (error 02, status 02, supply/return temperatures, kW, pump %).
- If there is no temperature difference between supply and return, the burner never ignited: check the gas valve is open, has power and opens; confirm inlet pressure and the 24 V at the valve during ignition.
- If there is a temperature difference, the flame went out after lighting: check ionization current, the ionization cable and electrode, and the minimum O2 setting.
- Check the gas valve plug and wiring.
Other codes on the same units
- E00 Poor flame formation (flame sensed with burner off)
- E04 Voltage interruption / error read-out interrupted
- E05 Adjustment error (listed in short reference)
- E12 High limit stat open
- E14 Supply sensor T1 fault
- E18 Maximum supply temperature exceeded
- E19 Maximum return temperature exceeded
- E28 Fan speed not reported back
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.