Rinnai · Boiler

E00 Poor flame formation (flame sensed with burner off)

High severity E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the control is telling you

Lockout: an ionization signal (flame) is detected although the boiler is not burning.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Likely causes

  • Short circuit in the ionization cable or electrode
  • 24 V short circuit in a connected component

Test and repair steps

  1. Unplug the ionization cable at the control unit and electrode; measure between the ionization lead and ground, reconnecting part by part until the short shows up.
  2. Repair or replace the part that causes the short.
  3. If a 24 V short is suspected: unplug all 24 V connections (fan, pump, three-way valve, 24 V plug on the connection block), restore power, then reconnect the parts one by one to find the shorted one.

Other codes on the same units

  • E02 No flame formation (ignition failure)
  • E04 Voltage interruption / error read-out interrupted
  • E05 Adjustment error (listed in short reference)
  • E12 High limit stat open
  • E14 Supply sensor T1 fault
  • E18 Maximum supply temperature exceeded
  • E19 Maximum return temperature exceeded
  • E28 Fan speed not reported back

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.