Daikin · Air handler

Ed2 System mismatch

Medium severity DX6VS / DZ6VSDV / DFVE

What the control is telling you

The indoor unit reports to the outdoor unit that the required airflow is above the indoor unit maximum, or that the indoor unit is not an EEV type. This is usually an uncertified combination or an airflow trim set too far.

Applies to: Outdoor DX6VS*361*A*, DZ6VS*361*A*, DX6VS*601*A*, DZ6VS*601*A* with listed indoor units (D*96VC0403B*, D*96VC0603B*, D*80VC0603B*, D*80VC0803B*, D*97MC0603B*, D*96SC0603BU*, MBVC1200*, D*96VC0804C*, D*97MC0804C*, D*80VC0804C*)

Likely causes

  • Airflow trim set to a prohibited value
  • Uncertified indoor unit connected to the outdoor unit
  • Required CFM above the indoor unit maximum after trimming
  • Indoor unit is not EEV type

Test and repair steps

  1. Check whether the outdoor and indoor combination is listed on the AHRI website. If not, replace it with a certified combination.
  2. Confirm the airflow trim setting has not been set to a prohibited value.
  3. Note the trim limits on DX6VS*361*A* / DZ6VS*361*A* trims above 10% are invalid; on DX6VS*601*A* / DZ6VS*601*A* trims above 5% are invalid. A trim that pushes CFM past the indoor limit also causes this error.

Other codes on the same units

  • 9b Low indoor airflow (with electric heat)
  • 70 EEV disconnection detected
  • 73 Liquid side thermistor abnormality
  • 74 Gas side thermistor abnormality
  • 75 Pressure sensor abnormality
  • b4 Blower motor current trip or lost rotor
  • b7 ID blower motor missing required parameters, fails to start
  • b9 Low indoor airflow (without electric heat)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 59. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.