Daikin · Air handler

Eb9 Indoor airflow below requirement

Medium severity DX6VSDZ6VSDV/DFVE

What the control is telling you

The estimated airflow from the motor is lower than the airflow the system needs. Thermostat shows B9.

Applies to: Indoor EEV air handler

Likely causes

  • Failed indoor blower motor
  • Indoor fan motor not properly connected
  • Too much static pressure

Test and repair steps

  1. Check ID fan motor wiring and connectors. Repair or replace if needed.
  2. Check the ID fan motor. Replace if needed.
  3. Check the duct work for obstructions.

Other codes on the same units

  • Eb0 Estimated indoor airflow near zero CFM

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: SiUS612209EA service instructions, p. 48. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.