Daikin · Air handler
b9 Low indoor airflow (without electric heat)
What the control is telling you
Blower feedback speed stays between 50 and 150 rpm with no electric heat demand. It triggers after 10 consecutive detections, or after 360 detections while checking 720 times.
Applies to: EEV air handler
Likely causes
- Fan or motor obstructed
- Blocked filters
- Restrictive or undersized ductwork
- Indoor motor or control board failure
Test and repair steps
- Turn off power before connecting or disconnecting connectors.
- Check whether anything is touching the blower or motor, or whether filters are blocked. Remove obstacles or clear the filters.
- Check the duct work for blockage. Remove any obstruction from the duct.
- Check whether the ducts are undersized. If external static pressure is above 0.5 inH2O (124.5 Pa), redesign the duct so it is below that value.
- If the problem remains, replace the control board or the motor.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 62. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.