Daikin · Air handler
70 EEV disconnection detected
What the control is telling you
The controller does not detect the indoor EEV coil connector at X3A.
Applies to: EEV air handler and EEV cased coil
Likely causes
- Indoor EEV coil not connected between control board and junction connector
- Incorrect wiring to the EEV
- Indoor control board failure
Test and repair steps
- Turn off power before connecting or disconnecting connectors.
- Check that the indoor EEV coil is connected between the control board and the junction connector. If not, connect the coil.
- Check the EEV wiring. Coil colors: orange pin 1, red pin 2, yellow pin 3, black pin 4, gray COM pin 6. If wiring is wrong, correct it.
- Measure coil resistance between pins 1-6, 2-6, 3-6 and 4-6. Each should read 40-50 Ω. If not, replace the EEV coil.
- If the problem remains, replace the control board.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 64. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.