Daikin · Air handler

b4 Blower motor current trip or lost rotor

Medium severity DV / DFVE

What the control is telling you

The blower motor reports a current trip or lost rotor through its control status flags.

Applies to: EEV air handler

Likely causes

  • Fan or motor obstructed
  • Filters blocked
  • Blockage in ductwork
  • Ducts undersized, external static pressure above 0.5 inH2O (124.5 Pa)

Test and repair steps

  1. Turn off power before connecting or disconnecting connectors.
  2. Check whether anything is touching the blower or motor, or whether filters are blocked. Remove obstacles or clear the filters.
  3. Check the duct work for blockage. Remove any obstruction from the duct.
  4. Check whether the ducts are undersized. If external static pressure is above 0.5 inH2O (124.5 Pa), redesign the duct so it is below that value.
  5. If the problem remains, replace the control board or the motor.

Other codes on the same units

  • 9b Low indoor airflow (with electric heat)
  • 70 EEV disconnection detected
  • b7 ID blower motor missing required parameters, fails to start
  • b9 Low indoor airflow (without electric heat)
  • Ed2 System mismatch

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 60. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.