Daikin · Air handler

b7 ID blower motor missing required parameters, fails to start

High severity DV / DFVE

What the control is telling you

The indoor blower motor does not have the parameters it needs to run and fails to start 40 times in a row.

Applies to: EEV air handler

Likely causes

  • Locked motor rotor
  • Wrong or missing shared data on the network

Test and repair steps

  1. Turn off power before connecting or disconnecting connectors.
  2. Check for a locked motor rotor. If found, remove obstacles from the blower or motor.
  3. Check the shared data on the network. If it is wrong or missing, rewrite the shared data.
  4. If the problem remains, replace the control board.

Other codes on the same units

  • 9b Low indoor airflow (with electric heat)
  • 70 EEV disconnection detected
  • b4 Blower motor current trip or lost rotor
  • b9 Low indoor airflow (without electric heat)
  • Ed2 System mismatch

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 61. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.