Daikin · Air handler
74 Gas side thermistor abnormality
What the control is telling you
The gas thermistor reads open or shorted, or its value or voltage is outside the normal range. Check at X15A, pins 1 and 2.
Applies to: EEV air handler, EEV cased coil
Likely causes
- Open or short circuit of the gas thermistor (X5A)
- Gas thermistor reading incorrect or outside normal range
- Indoor (ID) control board failure
Test and repair steps
- Turn off the power switch before connecting or disconnecting any connector.
- Check that the indoor gas thermistor is connected at the control board and junction connector.
- If it is not connected, connect the gas thermistor.
- Check the wiring to the gas thermistor and correct any faults.
- Measure the thermistor resistance and compare it with the resistance table.
- If the resistance is wrong, replace the gas thermistor.
- If the connection, wiring and resistance are correct, replace the control board.
Other codes on the same units
- 73 Liquid side thermistor abnormality
- 75 Pressure sensor abnormality
- E76 No outdoor unit or indoor unit communication
- E77 No thermostat communication
- E78 No outdoor unit or indoor unit communication
- Ed2 System mismatch
- EE Emergency operation indicator
- Ed Electric heater DIP switches not matched to heater kit
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin SiUS612209EA service instructions, p. 66. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.