Daikin · Air handler
E77 No thermostat communication
What the control is telling you
The EEV indoor unit has no communication with the thermostat. Shown on the EEV indoor unit display.
Applies to: EEV indoor units (air handlers and cased coils)
Likely causes
- Broken thermostat communication wires
- Faulty thermostat
Test and repair steps
- Check the thermostat wiring (terminals 1, 2, R and C).
- If the thermostat cannot be fixed right away, emergency mode may be used temporarily.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin SiUS612209EB service instructions, p. 32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.