Daikin · Air handler
Ed Electric heater DIP switches not matched to heater kit
What the control is telling you
Shown on the control board when emergency mode starts up. It means the DIP switches must be set to match the installed electric heater kit.
Applies to: EEV air handlers in emergency heating mode
Likely causes
- DS-3 heater kit DIP switches not set to the installed heater kit size
Test and repair steps
- Set DIP switches S-9 to S-12 on bank DS-3 using the Electric Heating Airflow table for the installed heater kit.
- The code clears once the switches are configured correctly.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin SiUS612209EB service instructions, p. 33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.