Daikin · Air handler

75 Pressure sensor abnormality

Medium severity DX6VS / DZ6VSDV**FEC / DFVE**CAPE(A)* / CHPE*

What the control is telling you

The indoor pressure sensor output is outside its normal range. Check the voltage at X16A, pins 3 and 4.

Applies to: EEV air handler, EEV cased coil

Likely causes

  • Open or short circuit of the pressure sensor (X16A)
  • Pressure sensor reading incorrect or outside normal range
  • Indoor (ID) control board failure

Test and repair steps

  1. Turn off the power switch before connecting or disconnecting any connector.
  2. Check that the indoor pressure sensor is connected at the control board and junction connector.
  3. If it is not connected, connect the pressure sensor.
  4. Check the wiring to the pressure sensor and correct any faults.
  5. Measure the sensor output voltage between pins 3 (black) and 4 (red) and compare it with the voltage vs pressure curve.
  6. If the voltage is wrong, replace the pressure sensor.
  7. If the connection, wiring and voltage are correct, replace the control board.

Other codes on the same units

  • 73 Liquid side thermistor abnormality
  • 74 Gas side thermistor abnormality
  • E76 No outdoor unit or indoor unit communication
  • E77 No thermostat communication
  • E78 No outdoor unit or indoor unit communication
  • Ed2 System mismatch
  • EE Emergency operation indicator
  • Ed Electric heater DIP switches not matched to heater kit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 67. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.