Daikin · Air handler
76 Indoor unit to outdoor unit / gas furnace / blower communication error (during operation)
What the control is telling you
The outdoor unit, gas furnace or modular blower drops off the node list after the system has reached system matching state. The error is reported as soon as the latest node list is received.
Applies to: EEV air handler, EEV cased coil (indoor unit)
Likely causes
- Open communication circuit
- Incorrect wiring between the outdoor unit, gas furnace or modular blower
- No power supply to the outdoor unit, gas furnace or modular blower
- Control board failure
Test and repair steps
- Turn off power before connecting or disconnecting connectors.
- Check that the communication circuit is connected. Connect it if it is open.
- Check the communication wiring for errors and correct any miswiring.
- Check that power is supplied to the outdoor unit, gas furnace or modular blower. Restore power if it is missing.
- If the wiring and power are good, replace the control board.
- Also follow the network troubleshooting steps on p. 71.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin SiUS612209EB Daikin Service Instructions, p. 68. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.