Daikin · Air handler
77 Indoor unit to thermostat communication error (start-up and during operation)
What the control is telling you
The thermostat is not recognised on the node list for 60 seconds after a node list is received. The 60-second count restarts if a new node list arrives during that time.
Applies to: EEV air handler, EEV cased coil (indoor unit)
Likely causes
- Incorrect wiring between the indoor unit and the thermostat. The system may show a communication error without code 77 on the indoor control board.
- Thermostat failure
- Power interruption (low voltage)
- Thermostat or control board failure
Test and repair steps
- Check the wiring between the indoor unit and the thermostat and correct any faults.
- Check that power is supplied to the outdoor unit, gas furnace or modular blower. Restore power if it is missing.
- Press and hold the LEARN button on the indoor control board for more than 5 seconds to re-establish the network. If the error clears and does not return, no further action is needed.
- If the error returns, replace the thermostat or the control board.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin SiUS612209EB Daikin Service Instructions, p. 69. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.