Viessmann · Heat pump · Pump/purge
Drain pump control in HEAT
What happens, in order
- A call for heat starts the outdoor unit; the indoor blower follows anti-cold blow.
- The pump does not start while the level switch is closed (no condensate).
- If the level switch opens, the pump starts in about 4 seconds.
- If the switch closes within 3 minutes, the pump runs 1 minute, then stops.
- If the switch stays open for 3 minutes, the blower stops, the EEV closes and the pump stops.
- If the switch closes after an EE alarm, the EEV opens, the blower starts and the pump stays off.
Timings and thresholds
| Item | Value |
|---|---|
| Pump start after level switch opens | about 4 seconds |
| Pump run after switch closes | 1 minute |
| Level switch open before shutdown | 3 minutes |
Codes you may see during this
Applies to: DLFSOAH09XAK, DLFSOAH18XAK
More Viessmann heat pump sequences
- Auto-restart after power failure · Startup
- Outdoor compressor start protection · Startup
- Outdoor condensing unit compressor start delay · Startup
- Start-up and indoor fan delay · Startup
- Forced cooling run · Cooling
- Defrost entry and exit · Defrost
- Drain pump control in COOL · Pump/purge
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH service manual, PDF p. 10. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.