Viessmann · Heat pump · Startup
Start-up and indoor fan delay
What happens, in order
- On start, the louver becomes active immediately.
- The indoor fan starts 7 seconds later.
- In HEATING mode the indoor fan follows the anti-cold blow function.
Timings and thresholds
| Item | Value |
|---|---|
| Louver active | immediately on start |
| Indoor fan start delay | 7 seconds |
Applies to: DLFSOAH09XAK, DLFSOAH18XAK
More Viessmann heat pump sequences
- Auto-restart after power failure · Startup
- Outdoor compressor start protection · Startup
- Outdoor condensing unit compressor start delay · Startup
- Forced cooling run · Cooling
- Defrost entry and exit · Defrost
- Drain pump control in COOL · Pump/purge
- Drain pump control in HEAT · Pump/purge
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH service manual, PDF p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.