Viessmann · Heat pump · Defrost
Defrost entry and exit
What happens, in order
- Once the compressor has run, record the lowest T3 reading from minute 10 to minute 15 as T30.
- Enter defrost if the compressor has run 29 minutes and T3 is below TCDI1, with T3 plus the offset reaching T30 or less.
- Enter defrost if the compressor has run 35 minutes and T3 is below TCDI2, with T3 plus the offset reaching T30 or less.
- Enter defrost if the compressor has run 29 minutes and T3 is below TCDI3 for three minutes.
- Enter defrost if the compressor has run 120 minutes and T3 is below 5°F (-15°C).
- Exit defrost when T3 rises above TCDE1, or T3 stays above TCDE2 for 80 seconds, or the unit has been in defrost for 10 minutes.
- Return to normal HEATING mode after defrost ends.
Timings and thresholds
| Item | Value |
|---|---|
| Compressor run before defrost check (case 1) | 29 minutes |
| Compressor run before defrost check (case 2) | 35 minutes |
| Compressor run before defrost check (case 3, T3 below TCDI3) | 29 minutes, T3 low for 3 minutes |
| Compressor run before defrost check (case 4) | 120 minutes |
| T30 sampling window | 10th to 15th minute after compressor start |
| T3 hold above TCDE2 to end defrost | 80 seconds |
| Maximum defrost time | 10 minutes |
Applies to: DLFSOAH09XAK, DLFSOAH18XAK heat pump mode
More Viessmann heat pump sequences
- Auto-restart after power failure · Startup
- Outdoor compressor start protection · Startup
- Outdoor condensing unit compressor start delay · Startup
- Start-up and indoor fan delay · Startup
- Forced cooling run · Cooling
- Drain pump control in COOL · Pump/purge
- Drain pump control in HEAT · Pump/purge
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH service manual, PDF p. 9. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.