Viessmann · Heat pump · Defrost

Defrost entry and exit

Vitocal IND-O

What happens, in order

  1. Once the compressor has run, record the lowest T3 reading from minute 10 to minute 15 as T30.
  2. Enter defrost if the compressor has run 29 minutes and T3 is below TCDI1, with T3 plus the offset reaching T30 or less.
  3. Enter defrost if the compressor has run 35 minutes and T3 is below TCDI2, with T3 plus the offset reaching T30 or less.
  4. Enter defrost if the compressor has run 29 minutes and T3 is below TCDI3 for three minutes.
  5. Enter defrost if the compressor has run 120 minutes and T3 is below 5°F (-15°C).
  6. Exit defrost when T3 rises above TCDE1, or T3 stays above TCDE2 for 80 seconds, or the unit has been in defrost for 10 minutes.
  7. Return to normal HEATING mode after defrost ends.

Timings and thresholds

ItemValue
Compressor run before defrost check (case 1)29 minutes
Compressor run before defrost check (case 2)35 minutes
Compressor run before defrost check (case 3, T3 below TCDI3)29 minutes, T3 low for 3 minutes
Compressor run before defrost check (case 4)120 minutes
T30 sampling window10th to 15th minute after compressor start
T3 hold above TCDE2 to end defrost80 seconds
Maximum defrost time10 minutes

Applies to: DLFSOAH09XAK, DLFSOAH18XAK heat pump mode

More Viessmann heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSOAH service manual, PDF p. 9. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.