Viessmann · Heat pump · Cooling
Forced cooling run
What happens, in order
- Compressor runs at the F2 frequency.
- Indoor fan runs in BREEZE mode.
- After 30 minutes the unit changes to AUTO at 75.2°F (24°C).
Timings and thresholds
| Item | Value |
|---|---|
| Forced cooling run time | 30 minutes |
Applies to: DLFSOAH09XAK, DLFSOAH18XAK
More Viessmann heat pump sequences
- Auto-restart after power failure · Startup
- Outdoor compressor start protection · Startup
- Outdoor condensing unit compressor start delay · Startup
- Start-up and indoor fan delay · Startup
- Defrost entry and exit · Defrost
- Drain pump control in COOL · Pump/purge
- Drain pump control in HEAT · Pump/purge
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH service manual, PDF p. 9. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.