Viessmann · Heat pump · Pump/purge

Drain pump control in COOL

Vitocal IND-O

What happens, in order

  1. A call for cool starts the indoor blower.
  2. When the compressor starts, the pump turns on and runs until the outdoor unit cycles off (single zone) or the indoor unit is thermal OFF (multi-zone).
  3. If the level switch opens, the pump stays on.
  4. If the switch closes within 3 minutes, the pump keeps running and no alarm is posted.
  5. If the switch stays open for 3 minutes, the blower stops, the EEV closes and the pump stops.
  6. If the switch closes after an EE alarm, the EEV opens, the blower starts and the pump runs with the compressor.

Timings and thresholds

ItemValue
Level switch open before shutdown3 minutes

Codes you may see during this

EH 0E

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

More Viessmann heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSOAH service manual, PDF p. 10. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.