Viessmann · Heat pump

EH 0E Water-level alarm malfunction

Medium severity Vitocal IND-O

What the control is telling you

Operation lamp flashes 13 times, timer lamp off. The level switch has been open too long. In HEAT or COOL, if the level switch stays open for 3 minutes the blower turns off, the EEV closes and the pump turns off.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK indoor units

Likely causes

  • Water level rise in the drain pan
  • Level switch malfunction

Other codes on the same units

  • EC 55 IGBT temperature sensor TH open or shorted
  • EC 56 Evaporator coil outlet temperature sensor T2B open or shorted
  • EH 03 Indoor fan speed outside normal range
  • EH 0b Communication error between display board and main board
  • EH 31 Upper indoor fan speed outside normal range
  • EH 32 Lower indoor fan speed outside normal range
  • EH 3A External fan DC bus voltage too low
  • EH 3b External fan DC bus voltage too high

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLFSOAH service manual, PDF p. 11, 15. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.