Viessmann · Heat pump · Startup

Auto-restart after power failure

Vitocal IND-O

What happens, in order

  1. The auto-restart module stores the settings before the power failure.
  2. After power returns, the unit resumes the previous settings (SWING excluded) once the delay ends.
  3. If the saved mode was FORCED COOLING, run COOLING for 30 minutes, then switch to AUTO at 75°F (24°C).
  4. If the unit was off before the power loss and must start, delay compressor start 1 minute.
  5. In all other cases, delay compressor restart 3 minutes.

Timings and thresholds

ItemValue
Resume after power returns3 minutes
Compressor delay if unit was off1 minute
Compressor restart in other cases3 minutes
FORCED COOLING run before AUTO30 minutes

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

More Viessmann heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSOAH service manual, PDF p. 10. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.