Viessmann · Heat pump · Startup
Auto-restart after power failure
What happens, in order
- The auto-restart module stores the settings before the power failure.
- After power returns, the unit resumes the previous settings (SWING excluded) once the delay ends.
- If the saved mode was FORCED COOLING, run COOLING for 30 minutes, then switch to AUTO at 75°F (24°C).
- If the unit was off before the power loss and must start, delay compressor start 1 minute.
- In all other cases, delay compressor restart 3 minutes.
Timings and thresholds
| Item | Value |
|---|---|
| Resume after power returns | 3 minutes |
| Compressor delay if unit was off | 1 minute |
| Compressor restart in other cases | 3 minutes |
| FORCED COOLING run before AUTO | 30 minutes |
Applies to: DLFSOAH09XAK, DLFSOAH18XAK
More Viessmann heat pump sequences
- Outdoor compressor start protection · Startup
- Outdoor condensing unit compressor start delay · Startup
- Start-up and indoor fan delay · Startup
- Forced cooling run · Cooling
- Defrost entry and exit · Defrost
- Drain pump control in COOL · Pump/purge
- Drain pump control in HEAT · Pump/purge
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH service manual, PDF p. 10. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.