Daikin · Mini-split · Startup
Trial operation after installation
What happens, in order
- Measure supply voltage and confirm it is within the specified range.
- For cooling trial, set the lowest programmable temperature. For heating trial, set the highest programmable temperature.
- Run the trial following the operation manual. Check that all functions and parts work, including louver movement.
- When finished, set the temperature to a normal level: 26 to 28°C (78 to 82°F) in cooling, 20 to 24°C (68 to 75°F) in heating.
- For cooling in winter or heating in summer, enter trial mode: press Temp and Mode together, press Temp to select "T", press Mode to confirm, then press On/Off.
- Stop trial mode with On/Off if needed. Some functions are not available in trial mode.
- If the system is not used for a while after install, turn off the circuit breaker to stop standby power draw.
Timings and thresholds
| Item | Value |
|---|---|
| Restart delay after the system is turned off | 3 minutes |
| Trial operation automatic stop | about 30 minutes |
Applies to: New installs and commissioning of FTXM-W/V units
Models
FTXM-W/V
More Daikin mini-split sequences
- Restart after power failure or breaker reset · Startup
- Hybrid cooling (COOL or DRY mode) · Cooling
- Defrost (reverse cycle) sequence · Defrost
- CLEAN drying cycle after COOL or DRY · Standby/shutdown
- INTELLIGENT EYE energy saving operation · Other
- NIGHT SET mode (after OFF TIMER is set) · Other
- Outdoor fan control · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SiUS042113EA Inverter Pair service manual, p. 162. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.