Daikin · Mini-split · Standby/shutdown

CLEAN drying cycle after COOL or DRY

FTXM WVJU9

What happens, in order

  1. After COOL or DRY stops, the unit starts CLEAN automatically.
  2. CLEAN runs FAN and HEAT operation to dry the inside of the indoor unit.
  3. The flaps may close to improve drying.
  4. The CLEAN cycle stops by itself.
  5. To stop CLEAN early, press the stop button twice.
  6. CLEAN does not run if the unit was switched off by OFF TIMER or from a smartphone.
  7. Indoor temperature and humidity may not match preference during CLEAN.

Timings and thresholds

ItemValue
CLEAN run time after COOL or DRY stops140 minutes

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Models

FTXM09WVJU9FTXM12WVJU9FTXM18WVJU9FTXM24WVJU9

More Daikin mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Room Air Conditioner Operation Manual, p. 17-18. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.