Daikin · Mini-split · Cooling
Hybrid cooling (COOL or DRY mode)
What happens, in order
- Select COOL or DRY with the MODE button on the remote.
- Run normal cooling until room temperature gets close to the target.
- Switch to hybrid cooling only part of the indoor heat exchanger is cooled.
- Cooled, dehumidified air mixes with room air so the room stays near target while dehumidifying.
- The cooled area is set automatically by how much moisture must be removed; a bigger moisture load means a bigger cooled area.
- If more cooling capacity is needed, the unit returns to normal cooling.
- In DRY mode, the indoor fan is also controlled automatically to help dehumidify.
Applies to: FTXM-W/V cooling and dry operation
More Daikin mini-split sequences
- Restart after power failure or breaker reset · Startup
- Trial operation after installation · Startup
- Defrost (reverse cycle) sequence · Defrost
- CLEAN drying cycle after COOL or DRY · Standby/shutdown
- INTELLIGENT EYE energy saving operation · Other
- NIGHT SET mode (after OFF TIMER is set) · Other
- Outdoor fan control · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SiUS042113EA service manual, pp. 42-43. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.