Daikin · Mini-split · Other

INTELLIGENT EYE energy saving operation

FTXM WVJU9

What happens, in order

  1. If no presence is detected for 20 minutes, energy saving starts and the INTELLIGENT EYE lamp goes off.
  2. In HEAT, the setpoint is lowered by the amount shown.
  3. In COOL or DRY, the setpoint is raised by the amount shown.
  4. If the room is above 86°F (30.0°C) in COOL or DRY, the setpoint is raised by a smaller amount.
  5. In FAN operation only, the airflow rate is lowered slightly.
  6. When movement is detected again, the lamp lights and energy saving ends.

Timings and thresholds

ItemValue
No presence before energy saving starts20 minutes
HEAT setpoint change-3.6°F (-2.0°C)
COOL setpoint change+3.6°F (+2.0°C)
DRY setpoint change+3.6°F (+2.0°C)
COOL or DRY change when room exceeds 86°F (30.0°C)+1.8°F (+1.0°C)
Sensor detection range23 ft (7 m), 110° horizontal, 90° vertical

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Models

FTXM09WVJU9FTXM12WVJU9FTXM18WVJU9FTXM24WVJU9

More Daikin mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Room Air Conditioner Operation Manual, p. 20-21, 23. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.