Daikin · Mini-split · Defrost
Defrost (reverse cycle) sequence
What happens, in order
- Defrost starts only in heating operation when the outdoor temperature and outdoor heat exchanger temperature meet the start conditions.
- The compressor must have run for 6 minutes before defrost can start.
- Enough accumulated run time must pass after start or the previous defrost; the value depends on the previous defrost.
- The unit switches to cooling cycle (reverse) with the four-way valve, and the outdoor fan is turned OFF.
- The compressor frequency is ramped to the defrost frequencies, and the electronic expansion valve follows its starting control and pulse zones.
- Defrost ends when the outdoor heat exchanger temperature or defrost time reaches the set limit.
Timings and thresholds
| Item | Value |
|---|---|
| Compressor run before defrost may start | 6 minutes |
| Frequency and valve ramp steps | 5 to 8 seconds |
Applies to: Heating operation, outdoor unit
Models
09/12 class18/24 class
More Daikin mini-split sequences
- Restart after power failure or breaker reset · Startup
- Trial operation after installation · Startup
- Hybrid cooling (COOL or DRY mode) · Cooling
- CLEAN drying cycle after COOL or DRY · Standby/shutdown
- INTELLIGENT EYE energy saving operation · Other
- NIGHT SET mode (after OFF TIMER is set) · Other
- Outdoor fan control · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.