Daikin · Mini-split · Defrost

Defrost (reverse cycle) sequence

FTXM-W/V

What happens, in order

  1. Defrost starts only in heating operation when the outdoor temperature and outdoor heat exchanger temperature meet the start conditions.
  2. The compressor must have run for 6 minutes before defrost can start.
  3. Enough accumulated run time must pass after start or the previous defrost; the value depends on the previous defrost.
  4. The unit switches to cooling cycle (reverse) with the four-way valve, and the outdoor fan is turned OFF.
  5. The compressor frequency is ramped to the defrost frequencies, and the electronic expansion valve follows its starting control and pulse zones.
  6. Defrost ends when the outdoor heat exchanger temperature or defrost time reaches the set limit.

Timings and thresholds

ItemValue
Compressor run before defrost may start6 minutes
Frequency and valve ramp steps5 to 8 seconds

Applies to: Heating operation, outdoor unit

Models

09/12 class18/24 class

More Daikin mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.