NIGHT SET mode (after OFF TIMER is set)
What happens, in order
- NIGHT SET starts automatically when the OFF TIMER is set.
- The airflow rate setting is kept.
- Run at the target temperature for the first hour.
- After one hour, in cooling raise the target slightly to avoid over-cooling.
- After one hour, in heating lower the target slightly to avoid over-heating.
- Operation stops at the set hour.
Timings and thresholds
| Item | Value |
|---|---|
| Time at target temperature before shift | first 1 hour |
| Cooling target shift after 1 hour | +0.5°C (+0.9°F) |
| Heating target shift after 1 hour | -2°C (-3.6°F) |
Applies to: FTXM-W/V with OFF TIMER
More Daikin mini-split sequences
- Restart after power failure or breaker reset · Startup
- Trial operation after installation · Startup
- Hybrid cooling (COOL or DRY mode) · Cooling
- Defrost (reverse cycle) sequence · Defrost
- CLEAN drying cycle after COOL or DRY · Standby/shutdown
- INTELLIGENT EYE energy saving operation · Other
- Outdoor fan control · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SiUS042113EA service manual, pp. 42, 47. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.