Outdoor fan control
What happens, in order
- Fan ON with compressor OFF to cool the electrical box when its temperature is high.
- Fan OFF during defrosting.
- Fan OFF 60 to 70 seconds after the compressor stops.
- In cooling at low outdoor temperature, fan speed is reduced to keep the pressure difference when it is low.
- Forced operation fan runs as in normal operation.
- POWERFUL operation fan speed is increased.
- Indoor/quiet outdoor unit operation fan speed is reduced on command.
- Fan ON when cooling, heating or dry operation starts; fan OFF when it stops.
Timings and thresholds
| Item | Value |
|---|---|
| Outdoor fan OFF delay after compressor stops | 60 to 70 seconds |
Applies to: Outdoor unit fan, all operating modes
Models
09/12 class18/24 class
More Daikin mini-split sequences
- Restart after power failure or breaker reset · Startup
- Trial operation after installation · Startup
- Hybrid cooling (COOL or DRY mode) · Cooling
- Defrost (reverse cycle) sequence · Defrost
- CLEAN drying cycle after COOL or DRY · Standby/shutdown
- INTELLIGENT EYE energy saving operation · Other
- NIGHT SET mode (after OFF TIMER is set) · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual, p. 82. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.