Daikin · General · Other

Sampling Mode for intake air below 33 F (1 C)

Daikin One Powered Ventilator

What happens, in order

  1. If intake air drops below 33 F (1 C), the controller enters Sampling Mode.
  2. The fan cycles 5 minutes on and 15 minutes off.
  3. The cycle continues until the intake temperature rises to about 34 F (2 C).

Timings and thresholds

ItemValue
Fan run5 minutes
Fan off15 minutes
Exit pointAbout 34 F (2 C)

Codes you may see during this

Lo° F

Applies to: DQ-P-16-100

Models

DQ-P-16-100

More Daikin general sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: IO-DPV installation manual, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.