AUTO operation switching and monitoring mode
What happens, in order
- The unit selects Air Purifying or Humidifying operation from the room temperature and humidity.
- If humidity is high, Air Purifying operation runs.
- When the air is clean and the target humidity is reached during humidifying, the unit waits about 5 minutes and then enters Monitoring mode.
- In Monitoring mode the fan starts and stops periodically while dust, odor and humidity are checked.
- If dust, odor or a humidity drop is detected, the unit runs at Quiet and Low airflow again.
- When humidifying stops because the set humidity is reached or the water supply lamp lights, air purifying continues.
Timings and thresholds
| Item | Value |
|---|---|
| Time from clean air and target humidity to Monitoring mode | about 5 minutes |
Applies to: MCKB70YSAU
Models
MCKB70YSAU
More Daikin general sequences
- Power-on and start-up · Startup
- Heater operation and fan run-on · Heating
- Optional heater accessory staging (DQ-P-70-AH-H) · Heating
- Humidifying filter drying after humidifying stops · Standby/shutdown
- Shutdown for prolonged non-use · Standby/shutdown
- Stopping operation · Standby/shutdown
- Damper open and close sequence with ventilator · Other
- Energy Savings mode sampling cycle (out-of-limit intake air) · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Daikin MCKB70YSAU installation & operation manual, p. 17, 20. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.